Compressed Air After Coolers

Air-Cooled Aftercoolers (Van Air AC Series)

Request Quote

In Van Air AC series air-cooled after-coolers, hot compressed air is introduced to the core as ambient air is drawn across it, leaving the exiting air cooler. AC series after-coolers are normally sized for a 15°F (or less) approach to ambient air. For example, a compressor discharges 250°F air and the after-cooler is located in 80°F ambient conditions. With a 15°F approach, the air exiting the after-cooler will be 95°F and saturated, and the moisture created by cooling from 250°F to 95°F will condense.

Features and Benefits

  • Horizontal or vertical flow directions
  • Galvanized steel cabinet
  • Open vented motor
  • Pressure drop less than 3 psi at 80-125 psig

Brochure

Features

  • Single pass design with smooth surface copper tubes minimizes fouling and allows lower pressure drop.
  • Counter-flow shell and tube design provides close approach temperature; gains maximum heat removal benefit from expensive cooling water.
  • Cooper heat exchanger surfaces provide excellent heat transfer.
  • Seamless shells have maximum rupture strength and corrosion resistance.
  • Tube rolled into tubesheet eliminates thermal stress.
  • Removable end bonnets facilitate cleaning and servicing.
  • Drain ports on shell side for easy maintenance.
  • Compact package provides smaller footprint.
  • Can be mounted in horizontal or vertical positions

Construction

  • Brass Shell & Baffles
  • Copper Tubes
  • Forged Brass End Hubs
  • Cast Iron End Bonnets
  • Steel Mounting Bracket

Ratings

  • 150 psig max @ 300°F Tube Side
  • 300 psig max @ 300°F Shell Side

Brochure

IPAC Water-Cooled Aftercoolers

Request Quote

1st paragraph change to: IPAC has been manufacturing custom Heat exchangers for over 40 years. Their customers are petrochemical and chemical companies, medical, industrial gas, pharmaceutical, and many other industries. These exchangers are applied in pressure and vacuum applications and involve both liquids and gas. We have supplied many of these in compressed air systems of all sizes, high temperatures and a range of pressures.

Standards

  • ASME Section VIII, Division 1
  • TEMA B, C &R
  • PED-European Pressure Equipment Directive (97/23/EC)
  • People Republic of China, Special Equipment (SELO). D1 & D2

Typical applications

  • Compressed Air
  • Machining works
  • Oil Coolers
  • Hydraulics
  • Approach/Trim Coolers

Design Features & Options

Codes:

  • ASME, U, R, & PP
  • TEMA B, C & R
  • PED (CE) European Directive
  • China Manufacturing License

Shell Diameters: Up to 144 inches

Shell Materials

  • Carbon Steel
  • Stainless Steel
  • Aluminum
  • Alloy Steel
  • Nickel Alloys
  • Copper Alloys

Tube Materials

  • 90/10 CuNi
  • 70/30 CuNi
  • Admiralty
  • Copper
  • Carbon Steel
  • Stainless Steel

*dmi uses HTRI© and Compress™ for Heat Exchanger Sizing